13.7 Venting and Air Intake Pipe

Inspect all venting and air intake pipe. Ensure that
all seams are sealed and suspension points secure.
Repair suspension points if any part of the venting
or combustion air pipe is sagging. Check to make
sure any insulation is not missing or in poor
condition. Replace as necessary. Check all venting
and air intake components to ensure they are in
good condition, gas tight and corrosion-free.

13.8 Maintenance Checklist

Installation Code and Annual Inspections: All
installations and service of ROBERTS GORDON

®

equipment must be performed by a contractor

qualified in the installation and service equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the
ROBERTS GORDON

®

manuals and all applicable

governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.

To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON

®

equipment and perform service where necessary,
using only replacement parts sold and supplied by
Roberts-Gordon LLC.

Annual Fall Start-Up

Follow entire start-up procedure at this time and check control settings and
operation.

The Vicinity of the Heater

Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.

See Page 6, Section 3.

Vehicles and Other
Objects

Maintain the clearances to combustibles.

Do not hang anything from, or place anything on, the heater.

Make sure nothing is lodged in between the heat exchanger or in the louvers.

Immediately remove objects in violation of the clearances to combustibles.

See Page 7, Section 4.

Vent Pipe/Terminals

Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.

The area must be free of dirt and dust.

Remove any carbon deposits or scale using a wire brush.

If the vent terminal has a screen built in, remove any dirt, dust or deposits
from the screen.

See Page 18, Section 8.

Cabinet Exterior

After installation, touch up scratches. Periodic paintings should be done
thereafter as required. Warning labels and logo labels should be legible and
accurate. Please contact Roberts-Gordon LLC or ROBERTS GORDON

®

independent distributor if you need replacement warning labels or logo labels
See Page 2, Figure 1 through Page 4, Figure 3.

Combustion Air Intake
Pipe

Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,
gaps in the sealed areas or corrosion.

The area must be free of dirt and dust.

Clean and reinstall as required.

See Page 18, Section 8.