Roberts Gorden 10081601NA Rev H 12/11 User Manual
Page 53

SECTION 8: C
OMMISSIONING
T
HE
CORAYVAC
®
S
YSTEM
47 of 62
Step 8.1.3 After setting end vent vacuums between
2.5" wc and 3.0" wc, while all the burners are still
operating, use the down arrow button on the VFD to
reduce the frequency of the output signal to the
pump. Reduce the frequency of the VFD until the
manometer at each of the end vents reads 1.0" wc -
1.2" wc, Make note of this frequency setting below.
The frequency is found on the VFD’s LCD screen.
1.0" w.c. - 1.2" wc VFD Frequency Setting
Step 8.1.4 Return to the PC and click the pump and
zones to "OFF".
Step 8.1.5 Using the procedure described
42, Section 7.1.1 through Section 7.1.5, alter the fol-
lowing parameters on the VFD:Return to the PC and
click the vacuum pump and three zones to "AUTO",
then click exit.
Parameter
Number
Parameter
Name
Factory
Default
New
Setting
P01
Line Voltage
01
01
P03
Start Method
01
05
P05
Standard
Speed
Source
01
(03) (0-10) Vdc
(04) (4-20) mA
P44
Password
225
Any #
000-999
P45
Speed at
Minimum
Signal
0.0Hz
Frequency
Setting noted
P46
Speed at
Maximum
Signal
60.0Hz
Frequency
Setting noted
Record Frequency Setting Here: