2 7

Gas Pipe Sizing Chart

I N S TA L L E R ’ S I N S TA L L AT I O N I N S T R U C T I O N S

Capacity Table for Natural Gas

cubic feet / hour

(table assumes .3 inch pressure drop, specific gravity of .60)

Nominal

Length of Pipe in Feet

Iron Pipe
Size
Inches

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/4

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1-1/4 1050

730

590

500

440

400

370

350

320

305

275

250

225

210

1-1/2 1600 1100

890

760

670

610

560

530

490

460

410

380

350

320

After determining the length of pipe required select the pipe size that will supply the
cubic feet per hour of gas required for the input rating of the Continuum 2424WC.
The formula for figuring the cubic feet per hour required is:

Gas Input of Continuum 2424(BTU/HR)

CFH =

Heating Value of Gas(BTU/FT

3

)

*Gas input requirement is on the water heater data plate
*The heating value of the gas can be obtained from the local Natural Gas Utility

Capacity Table for LP Gas

BTUH of undiluted liquified petroleum gases

(table assumes 11 inches of water column pressure at the inlet, .5 inch drop)

Nominal

Length of Pipe in Feet

Iron Pipe
Size
Inches

10

20

30

40

50

60

70

80

90

100

125

150

1/2

275

189

152

129

3/4

567

393

315

267

237

217

196

185

173

162

146

1

1071

732

590

504

448

409

378

346

322

307

275

252

1-1/4 2205 1496 1212 1039

913

834

771

724

677

630

567

511