2 0

This manual must be followed exactly.

1) Read the safety issues completely before installing the Continuum 2424WC.

2) This water heater is suitable for water (potable) heating or space heating.

- The piping connected to the Continuum 2424WC must be approved for use in

potable water systems.

- Toxic chemicals such as those used for boiler water treatment are NOT to be

introduced to the Continuum 2424WC.

- The Continuum 2424WC, if it will be used as a potable water source, it must

not be connected to a system that was previously used with a nonpotable
water heating appliance.

3) The Continuum 2424WC is not suitable for use as a pool or spa heater.

4) The dip switches on the computer board have been preset at the factory and

should not be readjusted without the express knowledge and involvement of
Rinnai.

5) Install the Continuum 2424WC outdoors only.

6) Maintain proper space around the unit for proper servicing and operation.

Minimum clearances from combustible materials are listed below.

Top of Heater

12

inches

Back of Heater

0

inch

Front of Heater

24

inches

Sides of Heater

6

inches

Ground

12

inches

DO NOT install the Continuum 2424WC under an overhang less than 3 feet
from the top of the unit. The area under any overhang greater than 3 feet
must be open on three sides.

7) Installer must install a Pressure relief valve. Pipe pressure relief discharge to a

drain or outside environment (see page 29).

I N S TA L L E R ’ S I N S TA L L AT I O N I N S T R U C T I O N S

-Warnings-