CAUTION

!

label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERiFY PROP-

ER OPERATiON AFTER SERViCiNg!

Section 5... the “ECO” lED

Section 6... the “mAiN VAlVE” lED

“System Sentinel” Troubleshooting guide

ECO is “open”. Allow tank to cool,

and reset. if ECO again trips, the

Thermostat/high limit is defective.

Replace as required.

is “ECO lED now illuminated?

is the Pilot Flame burning?

Refer to

Section 3...the “igNiTiON” lED; and Section

4...the “PilOT VAlVE”lED of Troubleshoot-

ing guide. Repair or replace components as

required.

T h e

ECO (Energy Cut-Off device) is

not tripped (open) and power is

being supplied to the “PV” termi-

nal on the gas Control Valve.

YES

YES

YES

NO

NO

NO

is the "ECO" lED illuinated?

is the Pilot Flame burning?

is the Spark ignitor operating?

(Can sparking be heard?)

ignition Control module is inoperative and

must be replaced.

main gas Valve is inoperative

and must be replaced.

is the inlet gas pressure at or below the

maximum as specified on the rating plate?

Check Continuity of Blue and White

wires between ignition Control module and

gas Control Valve. Repair or replace as

required to restore power to gas valve.

The ignition Control module is

providing 24 VAC between the

“mV” and “mV/PV” terminals on

gas Control Valve, and main Burn-

er should be operating

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

is the “mAiN VAlVE” lED illuminated?

is main Burner on?

is 24 VAC present between Blue

wire on “mV Terminal and White

wire on “mV/PV” terminal on gas

valve?

is 24 VAC present between Blue wire on

“mV Terminal and White wire on “mV/PV”

terminal on the ignition Control module?

The System Sentinel Panel is

defective and must be replaced.

The System Sentinel Panel is

defective and must be replaced.