System sentinel” troubleshooting guide – Rheem Commercial Power Direct Vent Water heater User Manual

Page 23

background image

Section 4... the “PilOT VAlVE” lED

“System Sentinel” Troubleshooting guide

is the Spark ignitor operating?

(Can sparking be heard?)

is the “igNiTiON” lED illuminated?

ignition Control module

is inoperable and must be

replaced.

is the Pilot Flame burning?

gas Control Valve

is inoperable and must

be replaced

i s

the inlet gas pres-

sure at or below the

maximum as speci-

fied on the rating

plate?

Check continuity of Brown wire

between ECO Device (inside of Ther-

mostat), and “PV” Terminal on gas

Control Valve. Repair or replace wire as

needed to restore power to “PV” Termi-

nal on gas valve.

Refer to Section 3...the “igNi-

TiON” lED in the Troubleshooting guide

The ignition Control module is in

the ignition sequence, and is pro-

viding 24 VAC power to the ECO

(Energy Cut-Off Device) inside of

the Thermostat

YES

YES

YES

YES

NO

NO

NO

NO

NO

Refer to Section 5...the “ECO” lED in

the Troubleshooting guide

NO

NO

is the “PilOT VAlVE” lED illuminated?

1. Remove ignition Cable and check for good conti-

nuity, replace if necessary.

2. Check ignitor Electrode gap for proper spacing

(1/8” to 5/32”). Correct if necessary.

3. Examine Ceramic insulator on Pilot Assembly

for cracks. Replace if cracks are evident.

is 24 VAC present between the Brown wire on “PV”

Terminal and gray ground wire on ignition Control

module?

is 24 VAC present between the Brown wire on “PV”

Terminal and White wire on “PV/mV” Terminal on

the gas Control Valve?

YES

YES

YES

YES

is the “ECO” lED

illuminated?

CAUTION

!

label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERiFY PROP-

ER OPERATiON AFTER SERViCiNg!

The System Sentinel Panel is

defective and must be replaced.