Gas piping – Rinnai REU-VA3237FFU User Manual

Page 20

background image

20

VA Series Indoor LS Manual

Pipe Sizing Procedure - Example

1. Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating

value of the gas (available from the local gas company). The gas input needs to include all gas products at
the location and the maximum BTU usage at full load when all gas products are in use.

Gas Input of Rinnai water heater (BTU / HR)

Cubic Feet per Hour (CFH) =

Heating Value of Gas (BTU / FT

3

)

2. Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe

length.

Example: The heating value of propane gas for your location is 2516 BTU / FT

3

. The gas input of the R94LSi is

190,000 BTU/HR. Additional appliances at the location require 75,000 BTU/HR.

Therefore the cubic feet per hour = (190,000+75,000) / 2516 = 105.3 FT

3

/ HR.

If the pipe length is 100 ft then the 3/4 inch pipe size capable of supplying 197 FT

3

/ HR of propane gas

will be adequate.

Pipe Sizing Table - Natural Gas

Pipe Sizing Table - Propane Gas

Pipe Size (inches)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/4

1

1 1/4

1 1/2

273

1060 1580

188

1090

151

873

129

747

114

662

104

600

95

368 552

89

343 514

83

322 482

79

304 455

70

269 403

63

244 366

58

224 336

54

514

353

284

243

215

195

179

167

157

148

131

119

109

102

726

583

499

442

400

209 313

Length

Length

Pipe Size (inches)

10

20

30

40

50

60

80

100

125

150

175

200

s

1/2 3/4 1 1

1/4

291

1150 2350

200

1620

160

1300

137

1110

122

985

110

892

101

821

94

372 763

89

349 716

84

330 677

74

292 600

67

787

632

541

480

434

400

608

418

336

287

255

231

212

197

185

175

155

140 265 543

Inlet Pressure: less than 2 psi (55 inches W.C.)
Pressure Drop: 0.3 inches W.C.
Specific Gravity: 0.60

Inlet Pressure: 11.0 inches W.C.
Pressure Drop: 0.5 inches W.C.
Specific Gravity: 1.50

Schedule 40 Metallic Pipe

cubic feet per hour

Schedule 40 Metallic Pipe

cubic feet per hour

Gas Piping

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas
type, the pressure drop in the system, the gas pressure supplied, and gas line type. Refer to the National Fuel
Gas Code, NFPA 54
, for proper gas line sizing. The below information is provided as an example.