Step 8

HD Troubleshooting

Step 8

Step 9

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Step 7

Is there a Call For Heat?

Is Disable connection intact?

Does the Pump come on?

Is 24VAC at the NC side of

the air pressure switch?

Is blower pressure setting

correct?

Does igniter prove?

Is air switch bouncing?

Call our Technical Service Department

1-800-947-2975 Outside California

1-800-627-2975 Inside California

Replace gas valve

Is inlet gas supply pressure

correct?

Replace air pressure switch.

Correct the blower

shutter setting.

NO

Check the switch, transformer

and/or line voltage

YES

Does the main power switch provide

power to the green power LED?

Is temperature controller

installed?

Reattach.

NO

YES

Check and correct power

connections at main terminal

block, circuit breaker panel or

pump relay.

NO

NO

YES

NO

YES

Is 24VAC at PS on ignition module?

Is connecting plug secure?

NO

NO

NO

YES

NO

Is the flame sensor signal to the

ignition module greater than 1 uA DC?

YES

The unit is okay

YES

YES

Replace HSI

NO

Adjust manifold gas

pressure.

NO

Correct wiring.

YES

YES

NO

YES

YES

Is Amp draw during heat-

up for HSI greater than

3.1 Amps?

NO

YES

Is there 120VAC at the pump or

pump relay contacts?

Is the unit running?

NO

Is manifold gas pressure

correct?

YES

NO

Install.

NO

Does the combustion air

blower come on?

Check and correct power

connections at main terminal
block, ignition module, circuit

breaker panel or blower relay.

Is there 120VAC at the blower or

blower relay contacts 1 and 5?

NO

NO

YES

Correct inlet gas supply pressure