TEMPERATURE CONTROL

The pool water temperature is controlled by the pool

thermostat.

The heater water temperature high limit is controlled by

the manual reset high limit.

PRESSURE SWITCH

The pressure switch, or heater actuator, ensures that

the heater operates only when the filter pump is in
operation. It is factory set at 1.75 PSI for deck level
installations. When the heater is located below the level
of the spa or pool, it may be necessary to reset the
pressure switch to compensate for the no-flow static
head. If it is necessary to reset the pressure switch, we
recommend the following procedure:

PRESSURE SWITCH ADJUSTMENT:

1.

Make sure the pool filter is clean before adjusting
the switch.

2.

Set the heater control to the OFF mode.

3.

Turn the filter pump on and confirm that the pressure
switch is closed (use a multimeter to check). If the
pressure switch fails to close, either the switch
setting is too high or the filter pump is not supplying
enough pressure.

4.

Turn the heater ON.

5.

Manually turn the pressure adjustment knob clock-
wise until the heater shuts off. (A flat screw driver may
be necessary if knob is too tight).

6.

Slowly turn the adjustment knob counter-clockwise
until the heater calls for heat again.

7.

Turn an additional 1/2 turn counter-clockwise.

8.

While the heater is running, check the adjustment by
turning the pump off and on several times. The
burners should shut off immediately when the pump
is turned off. If it does not, repeat the above steps until
proper operation is observed.

20

MODELS 2100-4001

SECTION 4/ SERVICING INSTRUCTIONS

GENERAL LOCATION OF CONTROLS

MODELS 926-1826

Inlet/Outlet

Pressure

Header

Switch

Unitherm

Electrical

Governor

Conn.

Hi-limit
control/
Temp. Control

Main Burner Gas Valve

Inlet/Outlet
Header w/Bypass
Pump

Electrical

Connection

Main Burner

Gas Valve

Manual On/Off Valve

Fig. #9261.1