beautypg.com

Raypak P-926 User Manual

Page 15

background image

15

HIGH & LOW GAS PRESSURE SWITCHES

Pressure switches sense either high or low gas

pressure and automatically shut down burners if abnor-
mal pressures exsist. Standard on Models 3001-4001.

PRESSURE
SWITCH

GAS MANIFOLD

Fig. #8236

ELECTRICAL WIRING

CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after
servicing.

DANGER - SHOCK HAZARD - Make sure electrical
power to the heater is disconnected to avoid potential
serious injury or damage to components.

NOTE: If it is necessary to replace any of the original
wiring, it must be replaced with 105° C wire or its
equivalent.

ELECTRONIC IGNITION

The intermittent ignition device conserves energy by

automatically extinguishing the pilot when desired tem-
perature is reached. When additional heat is needed, the
pilot re-ignites electrically, eliminating the fuel costs of
maintaining a constant pilot. To ensure safe operation,
the gas valve cannot open until the pilot relights and is
confirmed.

Model

w/out lockout

with lockout

926-1826 Natural Gas

Standard

Optional

926-1826 Propane

N/A

Standard

2100-4001 Natural Gas N/A

Standard

2100-4001 Propane

N/A

Standard

Heater must be electrically grounded and bonded in
accordance with local codes, or, in the absence of local
codes, with the latest edition of the National Electrical
Code, ANSI/NFPA 70.

Fig. #8929.1

This manual is related to the following products: