beautypg.com

No yes, No yes yes, Diagnostic readouts – Raypak 266A User Manual

Page 46

background image

46

Power On

Is the water

temperature displayed?

NO

YES

Push MODE

switch to select
"Pool" or "SPA"

Push Temp

arrow to scroll to

desired temperature

NO

Water temperature

and set

temperature

displayed?

YES

CFH

(call for heat) will

display briefly

SPK

(spark) will display

until pilot is lit

up to 2

minutes maximum

NO

NO

YES

YES

Flame icon displayed

and flashing?

(pilot lit and rectified)

Heater Fired?

END

• Check On/Off switch (under lid on control panel)
• Check for 120/240 volts to the transformer
(time clock, circuit breaker, wire connections)
• Check for 24 volts to Circuit Board (P6 connector)

REM and Water Temperature

displayed and flashing

(a remote control is controlling the heater)

Note: Disconnect the remote by turning the

remote function off. See page 35 for instructions.

NO

YES

Is SERVICE displayed and flashing?

Diagnostic Readouts

"SNS" - Temperature sensor out of range (replace sensor)

Verify power at MV on P-4 Terminal on digital circuit board.

Verify power to valve MV voltage. (Replace valve.)

Sensor Failure

Inspect thermister, wires, and connector at Terminal P1
Check resistance value of the thermister. Reference to chart below.
Replace thermister if not within 10% of values shown below.
If okay, replace Circuit Board.

Temp Degrees F 40 50 60 70 80 90 100 106
Resistance (k)

261.1 199.0 153.1 118.8 93.0 73.3 58.3 51.0

If okay, replace Circuit Board

Sensor resistance at various temperatures

PRS Pressure switch. Verify water flow and pressure

CLEAN FILTER / STRAINER - backwash if neccessary.

HL1

High limit switch. Verify water flow. Inspect internal

HL2

Thermostat (Unitherm Governor) and bypass valve.

ROL

Rollout Sensor - Check for blocked heat exchanger and soot.
Atmospheric Units - Replace fusible link.
Low NOx Units - Press manual reset button.

CLK

Fireman or Remote switch connected to safety loop is in the
OFF mode.

VNT

Vent switch open. Check connections to the board.
If extractor installed, troubleshoot extractor.

IGN

Ignition control failure. Check power at PV.

PLT

Pilot failure. Check spark (bad ignition circuit or hi-tension wire).
Verify gas to the heater. Verify valve operation (gas present at
tube fitting). Verify clean pilot orifice and clearance from
igniter to ground hood. If pilot is lit, verify that the flame is
rectified (the spark will be off)

DIGITAL CONTROL LOGIC - FLOW CHART

This manual is related to the following products: