SECTION 9: T
ROUBLESHOOTING
39
BURNER DOES NOT STAY LIT
Possible Cause
Try this....
Damaged wires between DSI
Replace wires as required.
module and sensing electrode.
Faulty DSI module.
Replace DSI module.
Cracked ceramic at the
Replace electrode.
sensing electrode.
Recirculation of
Check that the 3” (80 mm) inner vent pipe is completely sealed.
exhaust gases.
BURNER CYCLES ON AND OFF TOO QUICKLY
Possible Cause
Try this....
Anticipator setting on
Adjust the anticipator setting to 0.6. See Page 20, Figure 12.
the thermostat is too low
.18
.2
.25
.3
.4
.5
.7
.9