FIGURE 4: Horizontal Installations

FIGURE 5: 45° Tilted Installations

*All dimensions are from the reflector.

NOTE: All dimensions indicate the required safe distances from combustibles. Dimensions "C" and "E" DO
NOT indicate the required mounting height. The minimum mounting height is 7' (2133 mm), except for aircraft
hangars and public garages (See Page 11, Sections 3.5.1 and 3.5.2).

Flue clearances from combustibles are zero. It is not necessary to provide additional clearance on
penetrations through the wall or roof.

Know your model number. Model number is found on the rating tag.

F

B

A

C

24" Min. (609 mm)

B

Rating Tag

A

A

D

D

E

E

A

A

FF

Approx. 45°

24" Min. (609 mm)

Required safe distances from combustibles*

Inches

Metric (cm)

Model

A

B

C

D

E

F

A

B

C

D

E

F

CGTH-30

4

16

36

28

34

6

11

41

92

72

87

16

CGTH-40

4

18

48

30

34

6

11

46

122

77

87

16

CGTH-50

4

20

48

32

36

6

11

51

122

82

92

16