W415-0612 / C / 01.25.08

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

Example 6:

V

1

= 3 ft

V

2

= 6 ft

V

3

= 8 ft

V

T

=

V

1

+

V

2

+

V

3

= 3 + 6 + 8 = 17 ft

H

1

=

2

ft

H

2

=

2.5

ft

H

R

=

H

1

+

H

2

= 2 + 2.5 = 4.5 ft

H

O

= .03(four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

=

H

R

+

H

O

= 4.5 + 8.1 = 12.6 ft

H

T

+ V

T

= 12.6 + 17 = 29.6 ft

Formula 1:

H

T

< V

T

12.6 < 17

Formula 2:

H

T

+ V

T

< 35 feet

29.6 < 35

Since both formulas are met, this vent confi guration is
acceptable.

FIGURE 16

For vent confi gurations requiring more than zero 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 35 feet

ple venting confi gurations

See graph to determine the required vertical rise

V

T

for the

required horizontal run

H

T

.

TOP OR REAR EXIT VERTICAL TERMINATION