Field Wiring

The terminal base has connections for each of the eight relay
channels and an external supply to power field devices. Each relay
channel of the FP-RLY-420 has two terminals: N.O. (Normally
Open) and I.C. (Isolated Common). The external supply is not
needed for the internal operation of the FP-RLY-420; however,
you may connect an external supply to power field devices by
connecting to the V and C terminals of the terminal base. If you
connect an external supply to the V and C terminals, the total
current supplied cannot exceed 6 A.

Table 1 lists the terminal assignments for the signals of each
channel.

Table 1. Terminal Assignments

Chan-

nel

Terminal Numbers

N.O.

I.C.

V

sup

COM

0

1

2

17

18

1

3

4

19

20

2

5

6

21

22

3

7

8

23

24

4

9

10

25

26

5

11

12

27

28

6

13

14

29

30

7

15

16

31

32