Power control procedure – NEC RS-232C User Manual

Page 16

background image

(16/50)

Check code

BCC: Block Check Code
Refer to the section 4.5

“Check code” for a BCC calculation.


Delimiter

CR (0Dh): End of packet





7. Power control procedure

7.1 Power status read

1) The controller requests the monitor to reply a current power status.

Header

Message

Check code

Delimiter

SOH-'0'-Monitor ID-'0'-'A'-'0'-'6'

STX-'0'-'1'-'D'-'6'-ETX

BCC

CR


Header

SOH (01h): Start Of Header
'0' (30h): Reserved
Monitor ID: Specify the Monitor ID from which you want to get status.

Ex.) If Monitor ID is '1', specify 'A'.

'0' (30h): Message sender is the controller.
'A' (41h): Message Type is "Command".
'0'-'6' (30h, 36h): Message length is 6 bytes.

Message

STX (02h): Start of Message

'0'-'1'-'D'-'6': Get power status command.
ETX (03h): End of Message


Check code

BCC: Block Check Code

Refer to the section 4.5

“Check code” for a BCC calculation.

Delimiter

CR (0Dh): End of packet

2) The monitor returns with the current power status.

Header

SOH (01h): Start Of Header
'0' (30h): Reserved
'0' (30h): Message receiver is the controller.
Monitor ID: Indicate a replying Monitor ID.

Ex.)

When this byte is set to 'A', the replying Monitor ID is '1'.

'B' (42h): Message Type is "Command reply".
'1'-'2' (31h, 32h): Message length is 18 bytes.

Message

STX(02h):Start of Message
'0'-'2' (30h, 32h): Reserved data
'0'-'0' (30h, 30h): Result code

00: No Error.
01: Unsupported.

'D'-'6'(44h, 36h): Display power mode code
'0'-'0' (30h, 30h): Parameter type code is "Set parameter".
'0'-'0'-'0'-'4' (30h, 30h, 30h, 34h): Power mode is 4 types.
'0'-'0'-'0'-'1' (30h, 30h, 30h, 31h): Current power mode

Header

Message

Check code

Delimiter

SOH-'0'-'0'-Monitor ID-'B'-'1'-'2'

STX-'0'-'2'-'0'-'0'-'D'-'6'-'0'-'0'-'0'
-'0'-'0'-'4'-'0'-'0'-'0'-'1'-ETX

BCC

CR