Figure 2-2. basic hardware setup, Wiring power to the cvs-1450 device, Wiring power to the cvs-1450 device -9 – National Instruments NI CVS-1450 Series User Manual
Page 23
Chapter 2
Setup and Configuration
© National Instruments Corporation
2-9
NI CVS-1450 Series User Manual
Figure 2-2. Basic Hardware Setup
Wiring Power to the CVS-1450 Device
This section describes how to connect the NI desktop power supply.
For instructions on how to connect a separate main supply, refer to the
Connecting to a Separate Main Supply
section.
Caution
Do not connect the CVS-1450 device main power to a source other than
24 VDC ±10%. Do not connect the CVS-1450 device isolated power to a source less than
5 VDC or greater than 30 VDC. Doing so could damage the CVS-1450 device.
To connect power to the CVS-1450 device, refer to Figure 2-3 while
completing the following steps:
1.
Plug the 4-position connector from the power supply into the power
receptacle on the CVS-1450 device.
2.
Plug the power cord into the power supply.
3.
Plug the power cord into an outlet.
The CVS-1450 device ships with a factory-installed startup program that,
when the CVS-1450 device is connected to a camera and powered on,
acquires images and displays them on the monitor. If the images from the
camera display on the monitor, continue to the
Device to the Development Computer
section. If the images from the