Safety guidelines for hazardous locations – National Instruments FP-DO-403 User Manual

Page 9

background image

© National Instruments Corp.

9

[c]FP-DO-403

Do not use the [c]FP-DO-403 as the only isolating barrier
between human contact and working voltages higher than
250 V

rms

.

Operate the [c]FP-DO-403 only at or below Pollution
Degree 2. Pollution Degree 2 means that only nonconductive
pollution occurs in most cases. Occasionally, however, a
temporary conductivity caused by condensation must be
expected.

Operate the [c]FP-DO-403 at or below Measurement
Category II. Measurement Category II is for measurements
performed on circuits directly connected to the low-voltage
installation. This category refers to local-level distribution,
such as that provided by a standard wall outlet.

Safety Guidelines for Hazardous Locations

The [c]FP-DO-403 is suitable for use in Class I, Division 2, Groups
A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC
T4 and Ex nA IIC T4 hazardous locations; and nonhazardous
locations only. Follow these guidelines if you are installing the
[c]FP-DO-403 in a potentially explosive environment. Failing to
follow these guidelines may result in serious injury or death.

Caution

Make sure that all products you use in hazardous

locations are certified for such use. Refer to the product
label or visit

ni.com/certification

, search by model

number or product line, and click the appropriate link in
the Certification column.

Caution

Do not disconnect I/O-side wires or connectors

unless power has been switched off or the area is known
to be nonhazardous.

Caution

Do not remove modules unless power has been

switched off or the area is known to be nonhazardous.

Caution

Substitution of components may impair

suitability for Class I, Division 2.

Caution

For Zone 2 applications, install the FieldPoint

system in an enclosure rated to at least IP 54 as defined
by IEC 60529 and EN 60529.