Table 1. terminal assignments, Wiring for low-current applications – National Instruments FP-DO-403 User Manual

Page 4

background image

[c]FP-DO-403

4

ni.com

loads on the output channels, up to 2 A per channel.

1

Connect

the external power supply to multiple V and V

SUP

terminals and

to multiple C and COM terminals as needed to ensure that the
maximum current through any terminal is 2 A or less.

Install a 2 A maximum, fast-acting fuse (F2A 250V) between the
external power supply and the V

SUP

terminal on each channel.

Install a 2 A maximum, fast-acting fuse suitable for the load at the
V

OUT

terminal. Figure 3 shows fuses where appropriate.

Table 1 lists the terminal assignments for the signals associated
with each channel. Terminal assignments and wiring diagrams are
also listed on the side panel of the cFP-DO-403 and under the
slide-in card on the front of the FP-DO-403 module.

National Instruments recommends that you wire the external
power supply to multiple V

SUP

and COM terminals. Figure 3

shows how to connect two output channels to loads.

Wiring for Low-Current Applications

If your application requires 2 A or less combined current through
all channels of the [c]FP-DO-403, you can wire your application
as shown in Figure 3. Install a 2 A maximum, fast-acting fuse
(F2A 250V) between the external power supply and the V terminal
as shown.

1

Refer to the

Digital Output Circuit

and

Specifications

sections for the maximum

output current level on all channels.

Table 1. Terminal Assignments

Channel

Terminal Numbers

Channel

Terminal Numbers

V

OUT

V

SUP

COM

V

OUT

V

SUP

COM

0

1

17

18

8

9

25

26

1

2

17

18

9

10

25

26

2

3

19

20

10

11

27

28

3

4

19

20

11

12

27

28

4

5

21

22

12

13

29

30

5

6

21

22

13

14

29

30

6

7

23

24

14

15

31

32

7

8

23

24

15

16

31

32

This manual is related to the following products: