beautypg.com

Powerware 9125 Two-in-One UPS 6000 VA User Manual

Page 59

background image

TROUBLESHOOTING

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

53

Action

Possible Cause

Alarm or Condition

Bypass

UPS is in Bypass mode.

The equipment is transferred to utility power; however,
the utility power continues to be passively filtered by the
UPS. Check for one of the following alarms:
Overtemperature, Overload, or UPS Failure.
The UPS automatically returns online after the condition
is cleared. However, if the UPS transfers to Bypass mode
3 times in 1 hour, the UPS remains in Bypass mode until
the UPS On

|

button is pressed or the 1-hour timer

expires.
NOTE If Bypass mode is due to a UPS failure, frequency
conversion (FC) UPS models no longer convert the utility
frequency to the load.

Bypass

Bypass is not available. Input
voltage is not within ±12% of
nominal or input frequency is
not within ±3% of nominal.

The UPS is receiving utility power that may be unstable or
in brownout conditions. The UPS continues to supply
power to your equipment. If conditions worsen, the UPS
may switch to battery power.

Battery Service

The battery may be fully
discharged.

Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the battery.
After charging the battery, press and hold the

button

for 3 seconds; then check the

indicator.

If the

indicator is still on, see “UPS Maintenance” on

page 41 to replace the battery.

The battery is not connected
correctly or the battery
circuit breaker is open.

Verify that the internal batteries are installed correctly
(see page 16) and that the battery circuit breaker is in the
ON (

|

) position. Call your service representative if the

problem persists.

Site Wiring Fault
(North American
models only)

Ground wire connection does
not exist or the line and
neutral wires are reversed in
the wall outlet.

Have a qualified electrician correct the wiring.
To disable this alarm, see “Configuration” on page 35.

Overtemperature

UPS internal temperature is
too high. The UPS switches to
Bypass, allowing the UPS to
cool.

Clear vents and remove any heat sources. Ensure the
airflow around the UPS is not restricted. If the condition
persists, contact your service representative.

Overload

Continuous audible alarm

Power requirements exceed
UPS capacity (103–112% for
2 minutes; 112–150% for up to
30 seconds) or the load is
defective.

Remove some of the equipment from the UPS.
If the overload condition persists, the UPS automatically
shuts down.

This manual is related to the following products: