Turning the ups off, Initiating the battery test – Powerware 9125 Two-in-One UPS 6000 VA User Manual
Page 36
OPERATION
EATON Powerware
®
9125 Two-in-One UPS (5000/6000 VA) User’s Guide
S 164201513 Rev B
www.powerware.com
30
Turning the UPS Off
NOTE Pressing the Off
button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1.
Prepare your equipment for shutdown.
2.
Press and hold the Off
button for approximately three seconds.
The
μ
indicator begins to flash. The UPS switches to Standby
mode (if utility power is available) and removes power from your
equipment.
3.
Unplug or remove utility power from the UPS; the UPS shuts down
in five seconds. The bar graph and battery indicators flash briefly
prior to shutdown.
If you do not unplug or remove utility power from the UPS, it
remains in Standby mode.
Initiating the Battery Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode to
perform the battery test.
NOTE For an accurate battery test, test the UPS with at least 50% load applied to the UPS.
The UPS automatically performs a battery test every 30 days. If the UPS
switches to Battery mode, the UPS resets the timer.
To initiate a battery test, press and hold the
button for three
seconds. The UPS cycles the bar graph indicators twice, verifies the
battery converter, and schedules the battery test to occur within
24 hours.