beautypg.com

Powerware 9125 Two-in-One UPS 6000 VA User Manual

Page 58

background image

TROUBLESHOOTING

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

52

Table 11. Troubleshooting Guide

Alarm or Condition

Possible Cause

Action

The

indicator is not

on; the UPS does not start.

μ

The power cord is not
connected correctly.

Check the power cord connections.

The wall outlet is faulty.

Have a qualified electrician test and repair the outlet.

The main utility breaker is off.

Verify that the main utility breaker is on.

The

indicator is

flashing; power is not
available to your
equipment.

μ

The UPS is in Standby mode.

Press the On

|

button to supply power to the

connected equipment.

The UPS operates
normally, but some or all of
the protected equipment is
not on.

The equipment is not
connected to the UPS
correctly.

Verify that the equipment is plugged into the UPS
receptacle.
For hardwired models, contact a qualified electrician to
check connections to the power source.

The UPS does not provide
the expected backup time.

The batteries need charging
or service.

Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the battery.
After charging the battery, press and hold the

button

for 3 seconds; then check the

indicator.

If the

indicator is still on, see “UPS Maintenance” on

page 41 to replace the battery.

Battery circuit breakers are
in the OFF (O) position.

Switch the battery circuit breaker to the ON (

|

) position

for all connected battery cabinets.

Intermittent audible alarm

Battery

UPS on battery (see “Battery
Mode” on page 33 for more
information).

The UPS is powering the equipment with battery power.
Check the bar graph indicators for available battery
capacity and prepare your equipment for shutdown.

Intermittent audible alarm

Battery

The UPS does not detect any
batteries.

Verify that the internal batteries are installed correctly
(see page 16) and that the battery circuit breaker is in the
ON (

|

) position.

Warning - Low Battery

Three-minute battery
warning.

Three minutes or less of battery power remains
(depending on load configuration and battery charge).
Prepare for a shutdown. Save your work and turn off your
equipment.

Shutdown - Low Battery

Shutdown imminent.

Prepare equipment for shutdown.

This manual is related to the following products: