Hardwired UPS Installation
W A R N I N G
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
C A U T I O N
S
For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S
For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to
your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:
S
40A minimum circuit with short circuit and overcurrent protection
S
200–240 Vac
S
Single-phase
S
50/60 Hz
S
The breaker must be wall-mounted and be readily accessible to the
operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)