Powerware 9125 Two-in-One UPS 6000 VA User Manual
Page 31
INSTALLATION
EATON Powerware
®
9125 Two-in-One UPS (5000/6000 VA) User’s Guide
S 164201513 Rev B
www.powerware.com
25
To hardwire the UPS:
1.
If you are installing power management software, connect your
computer to the USB port or UPS communication port (see
page 37). For the communication port, use only the serial cable
supplied in the accessory kit.
2.
Switch off utility power at the distribution point where the UPS will
be connected. Be absolutely sure there is no power.
3.
Remove the wiring access cover and the conduit landing plate and
retain (see Figure 12).
Punch holes in the conduit landing plate for the input and output
conduit using a Greenlee
®
punch or similar device.
Battery Connector
Communication Port
Wiring Access Cover
Battery Circuit
Breaker
REPO Connector
USB Port
X-Slot Communication
Bay
Conduit Landing Plate
Figure 12. Hardwired UPS Rear Panel
4.
Pull the input and output wires through separate conduit, leaving
approximately 0.5m (2 ft) of exposed wire. Attach a flexible metal
fitting to the end of each conduit.
5.
Insert each conduit through a wiring access entry and attach the
conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the
end of each incoming wire.