PV500-47C 06/12

 

Duct Fitting Equivalent Length

Duct Pipe:

6” Duct

7” Duct

8” Duct

9” Duct

90º Elbow

8 feet

9 feet

10 feet

11 feet

90º Long Radius Elbow

5 feet

5 feet

5 feet

6 feet

45º Elbow

5 feet

5 feet

5 feet

5 feet

The following remote air duct information is provided for use in design calculations, if needed.

Remote Air Duct Specifications

Input Mbtu

Required

Air (SCFM)

Max Duct Loss

(inches Water)

1500 325 0.784

1800 390

1.11

2000 433 1.356


8.3

Remote Combustion Air Cap

A UL Listed air intake vent termination cap MUST be attached to the remote combustion air vent termination to
adequately protect the combustion air inlet from wind and weather. A UL Listed air intake termination cap is
available from PVI Industries and may have shipped with the water heater as a purchased option.

8.4 Vertical or Horizontal Remote Air Duct Termination

 Air inlet and exhaust vents should terminate in the same wind pressure area whenever possible.

 Air inlet must be located no less than 3 feet (0.91m) below the exhaust terminal if they are within 10 feet (3.05

m) of each other.

 If terminating through the roof, the air inlet must terminate at least 12 inches (0.3 m) above roof level and at

least 12 inches (0.3 m) above snow levels.

 If terminating through a sidewall, the air inlet must terminate at least 12 inches (0.3 m) above grade and/or at

least 12 inches (0.3 m) above normal snow levels.

Vertical Remote Air

Horizontal Remote Air


8.5

Remote Air Consideration for Combined Remote Air Ducting

Each water heater MUST have separate intake piping. Consult factory for common air intake pipe sizing.