beautypg.com

Durawatt, Electric water heater – PVI Industries PV 500-6 User Manual

Page 12

background image

DURAWATT

®

ELECTRIC WATER HEATER

PV500-6 09/07

12


























NOTE: Elements are

usually

wired to contactors in groups, in order to maintain an amperage draw of close to, but not more

than, 50 amps per contactor.


*Applications for 600V use a re-rated 480V element. Therefore, the 40W/in.

2

is rated for 14 kW instead of 9 kW.

KW-VOLTAGE

3

Ø AMPS PER ELEMENT

1

Ø AMPS PER ELEMENT

AMPS PER LEG

AMPS TOTAL

AMPS PER LEG

AMPS TOTAL

*14 kW-600V

13 1/2

13 1/2

*7 kW-600V

7

7

18 kW-480V

22

22

9 kW-480V

11

11

4.5 kW-480V

5 1/2

5 1/2

18

kW-240V

44 44 25 75

9

kW-240V

22 22 13 38

4.5

kW-240V

11 11 6 18

18

kW-208V

50 50 29 87

9

kW-208V

25 25 15 44

4.5 kW-208V

12 1/2

12 1/2

7

22

TABLE 2

TYPICAL CURRENT MEASUREMENT

FIGURE 11

FIGURE 12