beautypg.com

Boiler ratings & dimensions – PB Heat Gas/Oil Boilers User Manual

Page 44

background image

42

BOILER RATINGS & DIMENSIONS

11. BOILER RATINGS & DIMENSIONS

Table 11.1: Series LC/LCE Boiler Ratings

1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.

2 Net I=B=R water ratings based on an allowance of 1.15.

3 Net I=B=R steam ratings based on an allowance for LC-04 to LC-08=1.333, LC-09=1.323, LC-10=1.310, LC-11=1.298, LC-12=1.290,

LCE-13 to LCE-24=1.288.

4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping

systems, etc.

5 Combustion efficiency determined in accordance with The Hydronics Institute’s Testing and Rating Standard for Heating Boilers.

Gross

I=B=R

Output

Mbh

Boiler

Model

Number

LC-04

LC-05R

LC-05

LC-06

LC-07

LC-08

LC-09

LC-10

LC-11

LC-12

LCE-13

LCE-14

LCE-15

LCE-16

LCE-17

LCE-18

LCE-19

LCE-20

LCE-21

LCE-22

LCE-23

LCE-24

547

649

707

868

1029

1189

1350

1511

1672

1832

1966

2125

2284

2444

2603

2763

2922

3082

3256

3430

3604

3777

16.3

19.4

21.1

25.7

30.7

35.5

40.3

45.1

49.9

54.7

58.7

63.5

68.2

73.0

77.8

82.5

87.3

92.1

97.3

102.5

107.7

112.8

4.75

5.60

6.10

7.50

8.80

10.20

11.60

12.80

14.20

15.60

17.00

18.40

19.80

21.00

22.50

24.00

25.00

26.50

28.00

29.50

31.00

32.50

Boiler

H.P.

Oil

GPH

I=B=R Burner Capacity

686

808

881

1077

1273

1469

1664

1860

2056

2252

2464

2657

2850

3043

3236

3429

3622

3815

4027

4239

4451

4663

Gas

MBH

1708

2029

2208

2713

3217

3717

4250

4804

5367

5917

6358

6875

7388

7908

8421

8938

9454

9971

10533

11096

11658

12217

Steam

Sq. Ft.

I=B=R Net Ratings

410

487

530

651

772

892

1020

1153

1288

1420

1526

1650

1773

1898

2021

2145

2269

2393

2528

2663

2798

2932

Steam

MBH

476

564

615

755

895

1034

1174

1314

1454

1593

1710

1848

1986

2125

2263

2403

2541

2680

2831

2983

3134

3284

Water

MBH

83.7

83.7

83.7

83.7

83.6

83.6

83.6

83.6

83.6

83.6

83.5

83.5

83.5

83.5

83.5

83.5

83.5

83.5

83.6

83.6

83.7

83.7

Oil

Combustion Efficiency

81.2

81.2

81.2

81.1

81.1

81.1

81.1

81.1

81.1

81.1

81.0

81.0

81.0

81.0

81.0

81.0

81.0

81.0

81.1

81.1

81.2

81.2

Gas

SERIES LC/LCE BOILER RATINGS

Figure 11.1: Tankless Coil Pressure Drops