beautypg.com

Connect fuel piping, Warning – PB Heat Gas/Oil Boilers User Manual

Page 33

background image

A. GENERAL

1. Read the Burner Instruction Manual, supplied with

the boiler or with the burner if purchased separately.
Review applicable code requirements for burner and
fuel piping installations.

2. Install piping to allow removal of burner and access

to combustion chamber for cleaning or service.

B. INSTALL FUEL OIL PIPING

1. Place the fuel oil tank and install the piping in

accordance with NFPA-31 and all other applicable
codes.

2. General Guidelines for Oil Piping

a) Follow the guidelines in the Burner Manual for

sizing oil lines. Never use smaller than 1/2" OD
copper tubing.

b) Install manual shut-off valves on the suction line

at the burner and at the oil line entrance to the
building. If installing a shut-off valve on the
return line, you must provide an oil pressure
relief valve piped ahead of the shut-off valve and
discharged to the tank to prevent over-pressure
conditions.

c) Install a two-pipe oil distribution system when

possible. It will improve the reliability of the oil
delivery to the burner.

d) Use flare fittings when using copper tubing.

e) Provide an oil line filter in the suction line. Size

the filter for the suction gear capacity of the
burner oil pump if running a two-pipe system.

f)

If burner is above the top of the fuel oil tank,
install a check valve on the oil suction line at the
burner to prevent oil from evacuating the line. If
burner is below the top of the tank, install an
anti-siphon device to prevent oil flow should the
oil line break.

C. INSTALL GAS SUPPLY PIPING

1. Size the piping as required by the National Fuel Gas

Code, ANSI Z223.1 or as required by local codes.

a) Use Table 7.1 for sizing of natural gas for a

system pressure drop of 0.3 inch water column.

2. The standard gas train is designed for a maximum

pressure of 1/2 psig (14 inches water column). Make
sure the system regulator will not allow a higher
pressure to the Gas Control Train under any
conditions.

3. The minimum gas supply pressure is listed on the

Burner Rating Plate. Make sure the system regulator
and the piping are sized and adjusted properly to
provide this pressure under all conditions.

4. Install a Service Valve, Sediment Trap and Ground

Joint Union at the supply connection to the Gas
Control Train as shown in Figure 7.1. These are not
supplied with the boiler. Install them in accordance
with local codes.

5. Use only pipe joint compounds rated for use with

Liquefied Petroleum Gases.

D. TEST GAS SUPPLY PIPING

1. ISOLATE THE BOILER GAS CONTROL TRAIN

FROM THE SYSTEM DURING TEST:

a) Test pressure 1/2 psig or less – Close the Manual

Shut-Off Valve on the Boiler Gas Control Train.

b) Test pressure over 1/2 psig – Disconnect the gas

supply piping upstream of the Boiler Manual
Shut-Off Valve.

31

CONNECT FUEL PIPING

7. CONNECT FUEL PIPING

Figure 7.1: Gas Supply Connection to Boiler

Do not expose the Gas Control Train to excessive
pressure. The gas valves can be damaged. This could
result in explosion hazard and severe personal injury
or death.

Do not test gas supply piping with open flame. Use a
soap suds mixture brushed onto the pipe joints to
test for leaks.

WARNING