CONNECT FUEL PIPING

Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of

0.3 inch Water Column.

10

20

30

40

50

60

70

90

100

150

1050

730

590

500

440

400

350

320

305

250

1600

1100

890

760

670

610

560

490

460

380

3050

2100

1650

1450

1270

1150

1050

930

870

710

4800

3300

2700

2300

2000

1850

1700

1500

1400

1130

8500

5900

4700

4100

3600

3250

3000

2600

2500

2000

17500

12000

9700

8300

7400

6800

6200

5400

5100

4100

44000

31000

25000

22000

20000

18000

17000

15000

14000

11500

Pipe Length

(Feet)

1-1/4"

Pipe

1-1/2"

Pipe

2"

Pipe

2-1/2"

Pipe

3"

Pipe

4"

Pipe

6"

Pipe

Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed for
pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:

Specific Gravity

Multiply Capacity by:

1.10

0.50

1.04

0.55

1.00

0.60

0.962

0.65

0.926

0.70