3.1 AUDIBLE

ALARM


The TempTrac audible alarm is activated each time a connected alarm condition occurs. The following are
representative alarm conditions that may be connected to and activate the TempTrac audible alarm (some alarms may
be connected to and operate separately from the TempTrac on some products).

 High/low water temperature alarm

 Probe

failures

 External thermostat limit failure

 Flame

Failure

 High and low gas pressure

 Low

water


The audible alarm is silenced by pressing any button (alarm condition still present)

3.2 ALARM

RECOVERY


1. Probe failure alarm automatically ends after normal operation is re-established. Check connections before

replacing the probe.

2. Temperature

alarms

HA” and “LA” automatically stop as soon as probe 1 senses temperatures within normal

operating parameters.

3. Digital input 2 & 3 alarms recover when condition(s) listed above are normalized and any button is pressed (if

used). Resetting the alarm condition may require resetting individual safety devices or cycling main power switch.

4. RTC alarm stops after programming the real time clock.
5. RTF alarm requires the replacement of the real time clock.


For additional information, contact the PVI Industries Customer Service Dept at 800-784-8326.