9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

12-8

12.4.3

Meters Printout [Ctrl]+[M]

The [Ctrl]+[M] key sequence prints the current readings of the UPS system meters.
The Input area shows the phase‐to‐phase voltage, frequency, and phase current of
the incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the UPS. The
Bypass area shows the phase‐to‐phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I). Figure 12‐5 shows a sample
System Meters printout.

Input

Output

Bypass

Battery

VAB
480

VBC VCA

KW

505

KVA
530

IA

IB

IC

FREQ
60.0

PF

0.95

V

540

I
0

640

480 480

640

640

VAB
480

VBC

VCA

480

480

IA

IB

IC

480

480

480

IN

0

VAB
480

VBC

VCA

480

480

FREQ
60.0

KVA
400

KW

320

PF

0.80

Uninterruptible Power System

UPS System Normal
Alarm: None
Notice: None

03 NOV 1997 14:22:45

+

Figure 12‐5. System Meters Screen

12.4.4

System Information Printout [Ctrl]+[A]

The [Ctrl]+[A] key sequence prints a listing of all available serial data. This printout
contains the information shown on the Event History Log and System Meters screens
of the UPS (see Figure 12‐4 and Figure 12‐5).