INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual
S 164201244 Rev E www.powerware.com
A-13
Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)
Basic Unit Rating
PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load
PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load
Units
Rating 50/60 Hz
kVA/kW
500/400
500/450
625/500
625/562
Input and Output Voltage
Volts
400
400
400
400
AC Input to UPS Rectifier (0.95 Min. pF)
(3) Phases, (1) Neutral, (1) Ground
A
Amps*
880
910
1100
1138
Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current
AWG or kcmil
(each)
350
(4)
400
(4)
600
(4)
700
(4)
AC Input to MBC (UPS Bypass)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
722
722
902
902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
DC Input from Battery to UPS
(1) Positive, (1) Negative
C
Vdc
Amps @ (2.0V/cell)
384
1096
384
1234
384
1371
384
1542
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
400
(4)
500
(5)
400
(5)
700
(5)
AC Output to Optional SBM
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
E
Amps
722
722
902
902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
722
722
902
902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
NOTE