1 using the lcd screen, Using the lcd screen, Figure 8‐2. lcd screen – Powerware 9315 User Manual
Page 58
USING THE CONTROL PANEL
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual
S 164201244 Rev E www.powerware.com
8-2
8.1
Using the LCD Screen
The LCD screen at the top of the control panel provides an operator interface with the
UPS system. Figure 8‐2 identifies the display fields discussed in the following
sections.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
Meters
System
Load Amps
Events
Statistics
Graphics
Setup
Input
Output
Bypass
Battery
VAB
nnn
VBC
VCA
KW
nnn
KVA
nnn
IA
IB
IC
FREQ
nn.n
PF
0.nn
V
nnn
I
nn
Meters
nnn
nnn
nnn
nnn
nnn
VAB
nnn
VBC
VCA
nnn
nnn
IA
IB
IC
nnn
nnn
nnn
IN
nnn
VAB
nnn
VBC
VCA
nnn
nnn
FREQ
nn.n
KVA
nnn
KW
nnn
PF
0.nn
Battery
4 MAY 1999 09:25:42
48.6
Minutes
Versions
+
A
B
C
D
E
F
G
Figure 8‐2. LCD Screen
A
The UPS status area contains three lines that display the current UPS state. The first line shows the present
UPS operational mode. The second line shows the highest level of the current active alarms, and the third line
shows any notices the UPS has posted. (For more information about alarms and notices, see Chapter 11,
“Responding to System Events.”)
B
The battery charge box shows the minutes of battery capacity available.
C
The menu box shows the currently selected menu and lists the options available on that menu. The title at the
top of the menu box is also shown below on the menu bar (E). Press the and pushbuttons to scroll up and
down through the options in the menu box.
D
The currently selected option is highlighted in the menu box (C). Press the and pushbuttons to move the
highlight up or down. The data in the information area (G) changes accordingly.
E
The menu bar lists the titles of the menus. The menu title currently displayed in the menu box (C) is
highlighted. When you press the and pushbuttons to move the highlight left or right, the data in the menu
box (C) and the information area (G) change accordingly.
F
The time stamp shows the current date and time. This date and time are recorded in the Event Log when an
alarm or notice is activated.
G
The information area contains data about UPS status and operation. Select a menu option to display statistics
or graphics.