INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual
S 164201244 Rev E www.powerware.com
A-14
Table F. Input/Output Ratings and External Wiring Requirements (PW9315-700/500 and PW9315-750/562)
Basic Unit Rating
PW9315-750/500 at 0.8 Lagging pF Load
PW9315-750/562 at 0.9 Lagging pF Load
Units
Rating 50/60 Hz
kVA/kW
625/500
625/500
625/562
625/562
Input and Output Voltage
Volts
480
600
480
600
AC Input to UPS Rectifier (0.95 Min. pF)
(3) Phases, (1) Neutral, (1) Ground
A
Amps*
951
761
984
787
Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current
AWG or kcmil
(each)
400
(4)
350
(4)
500
(4)
350
(4)
AC Input to MBC (UPS Bypass)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
752
601
752
601
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(3)
350
(3)
DC Input from Battery to UPS
(1) Positive, (1) Negative
C
Vdc
Amps @ (2.0V/cell)
384
1370
384
1370
384
1542
384
1542
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
500
(6)
600
(6)
600
(6)
AC Output to Optional SBM
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
E
Amps
752
601
752
601
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(3)
350
(3)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
752
601
752
601
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(3)
350
(3)
NOTE