Powerware 9315 User Manual
Page 142
INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual
S 164201244 Rev E www.powerware.com
A-32
Table P. Output/Inverter Cabinet Customer Interface Connections
CUSTJ4 Terminal
Name
Description
1
Building Alarm 2
Programmable UPS alarm. Activated by a remote dry contact closure.
2
Building Alarm 2 Return
3
Building Alarm 3
Programmable UPS alarm. Activated by a remote dry contact closure.
4
Building Alarm 3 Return
5
Building Alarm 4
Programmable UPS alarm. Activated by a remote dry contact closure.
6
Building Alarm 4 Return
7
Building Alarm 5
Programmable UPS alarm. Activated by a remote dry contact closure.
8
Building Alarm 5 Return
9
Not Used
10
Not Used
CUSTJ2 Terminal
Name
Description
1
Relay 1 NC
General purpose normally‐open and normally‐closed relay contacts.
2
Relay 1 Commom
3
Relay 1 NO
4
Building Alarm 1
Programmable UPS alarm. Activated by a remote dry contact closure.
5
Building Alarm 1 Return
6
Relay 2 NC
General purpose normally‐open and normally‐closed relay contacts.
7
Relay 2 Common
8
Relay 2 NO
9
Not Used
10
Not Used
CUSTTB Terminal
Name
Description
1
CB3 - Aux #2
Circuit breaker CB3 auxiliary contact.
2
CB3 - Aux #2*
3
Not Used
4
Remote to Bypass
Dry contact used to activate remote transfer to bypass.
5
Remote to Bypass Return
6
Remote to UPS
Dry contact used to activate remote transfer to UPS.
7
Remote to UPS Return
8
Not Used
9
REPO
Dry contact used to activate REPO of UPS.
10
REPO Common