USING FEATURES AND OPTIONS
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual
S 164201244 Rev E www.powerware.com
10-4
10.4
Optional Relay Interface Module
The optional Relay Interface Module (RIM) uses relay contact closures to indicate the
operating status and alarm condition of the Parallel Capacity/Redundant system.
Figure 10‐2 shows the RIM with its four 15‐pin connectors labeled J1 through J4.
Figure 10‐2. RIM
The RIM can provide the following signals:
UPS AVAILABLE
Pins 1 and 12
Contacts are closed when the UPS is operating in Normal
mode or ready to supply the load.
UPS OFF LINE
Pins 3 and 13
Contacts are open when the UPS is offline. Contacts are
closed when the UPS is poerating Normal mode.
BATTERY WEAK
Pins 5 and 14
Contacts are closed when approximately two minutes of
battery time is remaining, before the critical load is lost.
UTILITY FAILURE
Pins 6 and 15
Contacts are closed when Utility Failure is detected.