Appendix e: modbus protocol, Appendix e modbus protocol – Phonetics 2000 User Manual
Page 101
101
Appendix E: Modbus Protocol
APPENDIX E
Modbus Protocol
Function 02 - Read Input Status
Address Word
0000 - 0001
Returns ok/alarm for each input queried. This is the current
input state, not the alarm status. It is one bit per input.
Function 04 - Read Input Registers
Address Word
0000 - 0028 Returns a 32 bit integer to represent the current input
value.
8 inputs, AC detect, and Battery level.
Function 03 - Read Holding Registers
Function 06 - Preset Holding Register
Function 10 - Preset Multiple Registers
Address Byte
01 System Parameters
00 Unit’s phone number 16
none
10 Dialing method
1 1:Tone 2:Pulse
Tone
12 Voice reps
1 0 to 10
3
14 Callback acknowledge
1 1:Yes 0:No
Yes
16 Max calling rounds
1 0 to 100
100
18 Rings till answer
1 1 to 20
1
1C Carrier wait time
1 0 to 60 sec
35