6 ups electrical characteristics (inverter output) – Liebert 130 kVA User Manual
Page 94

User Manual
Hipulse - Single Phase ‘1+N’ UPS System
130 kVA - 110V
74
9.6
UPS Electrical Characteristics (Inverter Output)
I N V E R T E R O U T P U T
Rated Power
kVA
130
Rated mains voltage j
Vac
380 - 400 - 415
Three phase with neutral
Frequency k
Hz
50 to 60
Rated Power at cos
φ
= 0.8
KVA
130
Rated Power at cos
φ
= 1
KW
104
Overload
%
150% FOR 60 sec
125% for 10 min
110% for 1 hr
Maximum non linear load
allowed l
-
100% Pn
Voltage stability, steady state test
m
%
± 1.5
Voltage stability, transient test n
%
± 5
Maximum rate of change of
frequency o
Hz
/sec
0.1
Note:
j
= Factory set 400V – 380V or 415V voltages with software setting
k
= Factory set at 50Hz ; 60Hz with software setting.
l
= EN50091-3 (1.4.58) crest factor 3.
m
= EN50091-3 (4.3.4).
n
= EN50091-3 (4.3.7) also for 0-100% load transient, restore time 20ms to ±1%.
o
= Factory set at 0.1Hz/ sec; upto 2 Hz/sec with software setting.