Hipulse - Single Phase ‘1+N’ UPS System
130 kVA - 110V
71
Chapter 9
Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
9.1
Conformity and Standard
The UPS has been designed to conform the following standards: IEC, EN
9.2
UPS Environmental
The UPS shall be able to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Environmental Characteristics
Units
Rated Power
kVA
130
Operating Temperature
ºC
0 to 45 ºC
Relative Humidity
%
= 90% at 31 ºC, Saliferrous, Humid
Altitude of operation
m
= 1000m above sea level
Storage/ transport temperature
ºC
-25 to 70 ºC
9.3
UPS Mechanical Characteristics
Mechanical
Characteristics
Units
130 kVA
6 pulse
Height
mm
1900
Width
mm
1400
Depth
mm
925
Ventilation
-
By internal intake fans
Cable entry
-
Bottom
Protection
IP
41