beautypg.com

Multiple heater manifold, Water line connections, Water (potable) heating and space heating – Lochinvar Commercial Gas Glass Lined Tanke Type Water Heater CG150 User Manual

Page 8: Thermometers (not supplied), Relief valve

background image

8

FIGURE 7

• Where a separate vent connection is not available and the vent

pipe from the heater must be connected to a common vent with

an oil burning furnace, the vent pipe should enter the smaller

common vent or chimney at a point above the large vent pipe.

MULTIPLE HEATER MANIFOLD

When horizontally manifolding two or more heaters vent as

shown in Figure 8. Refer to NFPA 54/ANSI Z223.1 for venting

multiple heaters.

FIGURE 8

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see pages

12 thru 17 of this manual) for typical methods of application for

the water heaters.

The water heater may be installed by itself, or with a separate

storage tank, on both single and two-temperature systems. When

used with a separate storage tank, the circulation may be either

by gravity or by means of a circulating pump. When a circulating

pump is used it is important to note that the flow rate should be

slow so that there will be a minimum of turbulence inside the heater.

If a water heater is installed in a closed water system, contact the water

supplier or local plumbing inspector on how to control this situation.

WATER (POTABLE) HEATING

AND SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, shall

NEVER be introduced into this system.

3. This unit may NEVER be connected to any existing heating

system or component(s) previously used with a non-potable

water heating appliance.

4. When the system requires water for space heating at

temperatures higher than required for domestic water purposes,

a tempering valve must be installed. Please refer to installation

diagrams on pages 12 thru 17 of this manual for suggested

piping arrangements.

5. These water heaters cannot be used in space heating

applications only.

CAUTION

A closed system will exist if a check valve (without bypass),

pressure reducing valve (without bypass), or a water meter

(without bypass) is installed in the cold water line between

the water heater and street main (or well).

Excessive pressure may develop in such closed systems,

causing premature tank failure or intermittent relief valve

operation. This is not a warranty failure. An expansion tank

or a similar device may be required in the inlet supply line

between the appliance and the meter or valve to compensate

for the thermal expansion of the water.

SYSTEM CONNECTIONS
The system installation must conform to these instructions and to

the local code authority having jurisdiction. Good practice requires

that all heavy piping be supported.

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in

the installation diagrams.

Thermometers are installed in the system as a means of detecting

the temperature of the outlet water supply.

RELIEF VALVE

This water heater is equipped with a combination

temperature-pressure relief valve that complies with the standard

for relief valves and automatic gas shutoff devices for hot water

supply system, ANSI Z21.22.

FOR SAFE OPERATION OF

THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE

REMOVED OR PLUGGED.

ASME ratings cover pressure relief capacities. CSA ratings cover

release rate with temperature actuation.

In addition to the appliance relief valve, each remote storage tank

which may be used in conjunction with this appliance shall also be

installed with a properly sized, rated and approved combination

temperature (ANSI) and pressure (ASME) relief valve(s).

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE

PRESSURE OR TEMPERATURE INTO THE STEAM RANGE,

WHICH MAY CAUSE SCALDING AT FIXTURES, TANK

EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS

TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.

Your local code authority may have other specific relief valve

requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE

TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID

SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE

REDUCED FROM THE SIZE OF THE VALVE OUTLET AND

MUST NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD

IT BE LOCATED IN FREEZING AREAS. DO NOT THREAD OR

CAP THE END OF THIS LINE. RESTRICTED OR BLOCKED

DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE

AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO

ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and

precautions.

This manual is related to the following products: