Do not subject the combination gas valve to inlet gas

pressures of more than 14.0” W.C. - natural gas. A service

regulator is necessary if higher gas pressures are encountered.

Manifold gas pressure in inches of water column is 3.5.

The gas pressure specified refers to flow pressure taken at

pressure tap of automatic gas valve while heater is operating.

HEATER WIRING

All electrical work must be installed in accordance with the latest

version of the National Electrical Code ANSI/NFPA No. 70,

FIGURE 10 - SINGLE UNIT WIRING DIAGRAM

must conform to all local code authority having jurisdiction.

AN

ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF

ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.

If any of the original wire as supplied with the appliance must be

replaced, use only type 105

0

C thermoplastic or equivalent. 250

0

C

type F must be used for the flame sensor leads and the spark

ignition cable must be high voltage 250

0

C.

Figures shown are valid for 0-2000 ft. installations. See

“HIGH ALTITUDE INSTALLATIONS” for deration requirements

over 2000 ft.