beautypg.com

Sidewall direct, Venting, Vent/air termination – sidewall – Lochinvar Condensing Boiler 1.5 User Manual

Page 21

background image

Installation & Operation Manual

3. Maintain clearances as shown in FIG.’s 4-1 thru 4-3,

pages 21 and 22. The vent termination should not be

located in traffic areas such as walkways, adjacent

buildings, operable windows, or doors. Also maintain

the

following:

a. Vent

must

terminate:

• At least 6 feet (1.8 m) from adjacent walls.

• Not less than 7 feet (2.1 m) above grade where located

adjacent to public walkways.

• No closer than 12 inches (305 mm) below roof

overhang.

• At least 3 feet (.9 m) above any forced air intake

within 10 feet (3 m).

• No closer than 4 feet (1.2 m) horizontally

from any door or window or any other gravity air

inlet.

b. Air inlet must terminate at least 12 inches (305 m)

above grade or snow line; at least 36 inches

(914 mm) below the vent termination.

c. Do not terminate closer than 4 feet (1.2 m)

horizontally from any electric meter, gas meter,

regulator, relief valve, or other equipment. Never

terminate above or below any of these within 4 feet

(1.2 m) horizontally.

4. Locate terminations so they are not likely to be damaged

by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.

12" MIN

GRADE OR
SNOW LINE

TO BOILER INTAKE
AIR CONNECTION

FROM BOILER VENT
PIPE CONNECTION

36" MIN
48" MAX

Figure 4-1 Sidewall Termination of Air and Vent

PVC/CPVC or ABS is acceptable air inlet pipe material.

NOTICE

4

Sidewall direct

venting

Vent/air termination – sidewall

Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death,
or substantial property damage.

A gas vent extending through an exterior
wall shall not terminate adjacent to a wall
or below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.

Installation must comply with local
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

Determine location

Locate the vent/air terminations using the following
guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page
17 of this manual.

2. You must consider the surroundings when terminating

the vent and air:
a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air

conditioning equipment or be objectionable.

b. The flue products will form a noticeable plume as

they condense in cold air. Avoid areas where the

plume could obstruct window views.

c. Prevailing winds could cause freezing of condensate

and water/ice buildup where flue products impinge

on building surfaces or plants.

d. Avoid possibility of accidental contact of flue

products with people or pets.

e. Do not locate the terminations where wind eddies

could affect performance or cause recirculation,

such as inside building corners, near adjacent

buildings or surfaces, window wells, stairwells,

alcoves, courtyards, or other recessed areas.

ƽ WARNING

ƽ WARNING

NOTICE

ƽ WARNING Do not connect any other appliance to the

vent pipe or multiple boilers to a common
vent pipe except as noted in Section 2
on page 18. Failure to comply could
result in severe personal injury, death, or
substantial property damage.

f. Do not terminate above any door or above or

below any window. Condensate can freeze, causing

ice

formations.

g. Locate or guard vent to prevent condensate

damage to exterior finishes.

ƽ WARNING Sidewall vent and air inlet terminations

must terminate in the same pressure
zone.

21

ƽ CAUTION

Sidewall venting commercial products will
result in large exhaust plumes in cold
climates. Consideration should be taken
when locating in proximity to windows,
doors, walkways, etc.

This manual is related to the following products: