General information, Single-wall heat exchanger, Operating restrictions – Lochinvar SQUIRE SDT/SET065 - 119 User Manual

Page 4: Table 1a component materials, Sdt/set installation & operation manual

background image

1

General Information

The Lochinvar SDT/SET series indirect water heater
(FIG. 1-1) is designed to generate domestic hot water in
conjunction with a solar panel using forced circulation with a
backup heat source. This indirect water heater consists of a
316L Stainless Steel tank in which a smooth 304L stainless
steel coil is located (Table 1A). Solar heating fluid is pumped
through the coil and heats the water in the tank. If the solar
panel cannot produce enough heat, the backup source should
supply hot water. This tank is not intended for use in pool
heating applications or for heating any fluid other than water.
It is also not intended for use in gravity hot water heating
systems.

Table 1A

Component Materials

Component

Material

Tank

316L Steel Stainless Steel

Coil

304L Stainless Steel

Insulation

Polyurethane

Jacket

ABS

Figure 1-1 Lochinvar SDT and SET Series Indirect Water Heaters

PART NO.

“A”

(in.)

“G”

(in.)

“F”

(in.)

“E”

(in.)

“D”

(in.)

“C”

(in.)

“B”

(in.)

“I”

(in.)

“H”

(in.)

SDT065

SET119

SET090

SET065

SDT119

SDT080

3 5/16

3 5/16

3 5/16

3 5/16

3 5/16

3 5/16

9 1/8

9 3/8

9 1/8

9 1/8

9 3/8

9 1/8

27 15/16

27 15/16

27 15/16

27 15/16

31 11/16

31 11/16

33 5/8

N/A

37 7/16

40 3/16

N/A

N/A

N/A

N/A

N/A

47 3/16

54 1/2

53 3/4

52 5/16

61 13/16

61 13/16

52 5/16

60 1/8

60 1/8

59 7/8

69 3/8

59 7/8

68 3/16

69 3/8

68 3/16

59 7/8

59 7/8

59 7/8

N/A

N/A

N/A

24

24

28

24

24

28

921

820

1268

921

820

1268

1. RELIEF VALVE CONNECTION

2. HOT WATER OUTLET

3. BOILER WATER IN

4. BOILER WATER OUT

5. DRAIN / COLD WATER INLET

6. SOLAR WATER IN

7. SOLAR WATER OUT

8. ELEMENT

“I”

“I”

22.5

o

45

o

SOLAR ELECTRIC

SOLAR DUAL

COIL

2

5

7

6

8

1

5

7

6

8

3

1

2

1 - 1/2” FPT

1 - 1/2” FPT

1 - 1/2” MPT

1 - 1/2” MPT

AQUASTAT WELL

SOLAR SENSOR

SOLAR SENSOR

3/4” FPT

3/4” FPT

1” MPT

1” MPT

1” MPT

1” MPT

1” MPT

1” MPT

WEIGHT

FULL OF WATER

(LBS)

22.5

o

45

o

“A”

“B”

“C”

“H”

“F”

“G”

“A”

“B”

“C”

“D”

“E”

“F”

“G”

1” MPSF

Single-Wall Heat Exchanger

National Standard Plumbing Code

Single-wall heat exchangers in water heaters comply with the
National Standard Plumbing Code provided that:

boiler water (including additives) is practically non-toxic,
having a toxicity rating or class of 1, as listed in Clinical
Toxicology of Commercial Products, and

boiler water pressure is limited to a maximum of 30 psig by
approved relief valve.

Uniform Plumbing Code

Single-wall heat exchangers are permitted if they satisfy all of
the following requirements --

1.

The heat transfer medium is potable water or contains only
substances which are recognized as safe by the U.S. Food
and Drug Administration.

2.

The pressure of the heat transfer medium is maintained less
than the normal minimum operating pressure of the
potable water system.

3.

The equipment is permanently labeled to indicate that
only additives recognized as safe by the FDA shall be used
in the heat transfer medium.

Other heat exchanger designs may be permitted where
approved by the Administrative Authority.

Operating Restrictions:

Maximum domestic hot water temperature is 194°F.

Maximum boiler water temperature is 210°F.

Maximum working pressure for the vessel tank is
150 psig.

SDT/SET Installation & Operation Manual

4