High output piping, Table 9c parallel configuration, Sdt/set installation & operation manual – Lochinvar SQUIRE SDT/SET065 - 119 User Manual

Page 27: Friction loss sdt paralleel

background image

SDT/SET Installation & Operation Manual

27

9

High Output Piping

(continued)

PRESSURE

REDUCING VALVE

PRESSURE

GAUGE

BACKFLOW

PREVENTER

MAKE UP WATER

SYSTEM

SUPPLY

SENSOR

AIR

SEPARATOR

TO

SYSTEM

BALL VALVE

(TYPICAL)

SYSTEM

CIRCULATOR

EXPANSION

TANK

DRAIN POINT

(TYPICAL)

FROM

SYSTEM

COLD

WATER

IN

ANTI-SCALD

MIXING VALVE

HOT

WATER

OUT

TEMPERATURE/

PRESSURE

RELIEF VALVE

BOILER

TANK SENSOR/

AQUASTAT

SOLAR SENSOR

NOT TO EXCEED 4 PIPE DIA. OR

A MAXIMUM OF 12 “ APART

Y-STRAINER

(RECOMMENDED)

DOMESTIC

HOT WATER

CIRCULATOR

BOILER

CIRCULATOR

BOILER BACKUP

HEAT EXCHANGER

(SDT MODELS ONLY)

UNION

(TYPICAL)

TEMPERATURE/

PRESSURE

GAUGE

DRAIN

PRESSURE

RELIEF VALVE

KNIGHT

BOILER

SQUIRE

SOLAR

HEAT EXCHANGER

DRAIN

(FIELD SUPPLY)

CHECK VALVE

RECIRCULATION

PUMP

Figure 9-2 Indirect Boiler with Parallel Piping

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

Table 9C

Parallel Configuration

Model

Boiler

Flow

GPM

Boiler

Loop

Temperature

Continuous

Draw

GAL/HR

First Hour

Rating

GAL

Max Input

BTU/HR

SDT065

20

180° F

338

396

269,840

SDT080

20

180° F

344

414

269,840

SDT119

20

180° F

466

567

336,198

Table 9D SDT Parallel Friction Loss

FRICTION LOSS SDT PARALLE

6

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

6

FT/HD

FLOW

FRICTION LOSS SDT PARALLEEL

119

065 & 080

065 & 080

119

60

70

80

065

&

080

119

EL

10

0

20

30

40

50

60

70

80