High output piping, Table 9c parallel configuration, Sdt/set installation & operation manual – Lochinvar SQUIRE SDT/SET065 - 119 User Manual
Page 27: Friction loss sdt paralleel
SDT/SET Installation & Operation Manual
27
9
High Output Piping
(continued)
PRESSURE
REDUCING VALVE
PRESSURE
GAUGE
BACKFLOW
PREVENTER
MAKE UP WATER
SYSTEM
SUPPLY
SENSOR
AIR
SEPARATOR
TO
SYSTEM
BALL VALVE
(TYPICAL)
SYSTEM
CIRCULATOR
EXPANSION
TANK
DRAIN POINT
(TYPICAL)
FROM
SYSTEM
COLD
WATER
IN
ANTI-SCALD
MIXING VALVE
HOT
WATER
OUT
TEMPERATURE/
PRESSURE
RELIEF VALVE
BOILER
TANK SENSOR/
AQUASTAT
SOLAR SENSOR
NOT TO EXCEED 4 PIPE DIA. OR
A MAXIMUM OF 12 “ APART
Y-STRAINER
(RECOMMENDED)
DOMESTIC
HOT WATER
CIRCULATOR
BOILER
CIRCULATOR
BOILER BACKUP
HEAT EXCHANGER
(SDT MODELS ONLY)
UNION
(TYPICAL)
TEMPERATURE/
PRESSURE
GAUGE
DRAIN
PRESSURE
RELIEF VALVE
KNIGHT
BOILER
SQUIRE
SOLAR
HEAT EXCHANGER
DRAIN
(FIELD SUPPLY)
CHECK VALVE
RECIRCULATION
PUMP
Figure 9-2 Indirect Boiler with Parallel Piping
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
Table 9C
Parallel Configuration
Model
Boiler
Flow
GPM
Boiler
Loop
Temperature
Continuous
Draw
GAL/HR
First Hour
Rating
GAL
Max Input
BTU/HR
SDT065
20
180° F
338
396
269,840
SDT080
20
180° F
344
414
269,840
SDT119
20
180° F
466
567
336,198
Table 9D SDT Parallel Friction Loss
FRICTION LOSS SDT PARALLE
6
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
6
FT/HD
FLOW
FRICTION LOSS SDT PARALLEEL
119
065 & 080
065 & 080
119
60
70
80
065
&
080
119
EL
10
0
20
30
40
50
60
70
80