44 Ceiling Cassette Air Conditioner

Troubleshooting Guide

Troubleshooting CH32, CH33

32

33

D-pipe (Inverter)

temp. high

(105°C(221°F)

)

D-pipe (Constant)

temp. high

(105°C(221°F)

)

• Discharge sensor

(Inverter) temp. high

• Discharge sensor

(Cons.) temp. high

• Check the discharge pipe sensor for INV.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.

• Check the discharge pipe sensor for Cons.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.

Display

code

Title

Cause of error

Check point & Normal condition

Check Point

• CH 32

1. Check the install condition for over load.

2. Check the SVC V/V open.

3. Check the leakage of refrigerant.

• CH 33

1. Check the install condition for over load.

2. Check the SVC V/V open.

3. Check the leakage of refrigerant.

4. Check the constant compressor. (same with CH21)

90

°C

(194

°F)

80

°C

(176

°F)

95

°C

(203

°F)

Inverter

Constant

105

°C

(221

°F)

105

°C

(221

°F)

COMP OFF

COMP OFF

LEV OPEN

LEV OPEN

NORMAL

NORMAL

LEV OPEN/Hz down

LEV OPEN/Hz down

90

°C

(194

°F)