Drain pipe work, Caution, Service manual 27 installation – LG LCN240CP User Manual

Page 27: Drain piping of ceiling cassette, Drain test

background image

Service Manual 27

Installation

7. Drain Pipe Work

Drain Piping of Ceiling Cassette

• Drain piping must have down-slope (1/50 to 1/100): be sure not to

provide up-and-down slope to prevent reversal flow.

• During drain piping connection, be careful not to exert extra force

on the drain port on the indoor unit.

• The outside diameter of the drain connection on the indoor unit is

32mm(1.26inch).

• Be sure to install heat insulation on the drain piping.

Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings

The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump
operation:

• Connect the main drain pipe to the exterior and

leave it provisionally until the test comes to an end.

• Feed water to the flexible drain hose and check the

piping for leakage.

• Be sure to check the drain pump for normal operat-

ing and noise when electrical wiring is complete.

• When the test is complete, connect the flexible

drain hose to the drain port on the indoor unit.

Heat insulation material: Polyethylene foam with
thickness more than 8 mm(0.31inch).

Drain test

Maintenance
drain port

Upward
routing
not allowed

Pipe clamp

Indoor unit

Flexible drain hose

700mm

(27.6inch) or less

1 -1.5m(3.32-4.92ft)

300mm

(11.81inch) or less

Clamp metal(attached)

Drain hose(attached)

Drain raising pipe

Feed water

Drain Pump

Drain pan

Flexible drain hose
(accessory)

Main
drain pipe

Glue the joint

Drain
port

Drain hose connection
Use the clip (accessory)

Flexible drain hose

CAUTION

The supplied flexible drain hose should not be curved,
neither screwed. The curved or screwed hose may
cause a leakage of water.

1/50~1/100

MAX 700mm
(27.6inch)

Flexible drain hose

Flexible drain hose

■ Install the drain raising pipes at a right angle to the

indoor unit and no more than 300mm(11.81inch) from
the unit.

2. Tape the Pipings and Connecting cable from bot-

tom to top.

3. Form the pipings gathered by taping along the

exterior wall, and make the trap prevent water
from entering into the room.

4. Fix the pipings onto the wall by saddle or equiva-

lent.

In case of the Outdoor Unit being installed
above position of the Indoor Unit.

Seal a small opening
around the pipings
with gum type sealer.

Trap