When cooling does not operate trouble 3 – LG LCN240CP User Manual

Page 35

background image

Service Manual 35

Troubleshooting Guide

When cooling does not operate

Trouble 3

Turn on Main Power

Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 1°C at least.

When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.

Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).

When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.

• Check the indoor temperature sensor is disconnected or not(About 10k

Ω / at

25°C(77°F)).

Check Relay(RY - COMP) for driving compressor.

• When the power(About AC208V-230V) is applied to the connecting wire

terminal support transferred to compressor, PWB Ass'y is normal.

• Check the circuit related to the relay.

Check point

COMP ON

COMP OFF

Below DC 1V

About DC12V

(app)

Between two pin of DC
part in relay for COMP