Service Manual 41

Troubleshooting Guide

Troubleshooting CH04

Check the resistance

0

CN Float

04

Drain pump

/ Float switch

• Float switch Open.

(Normal : short)

• The connection of wire(Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)

Display

code

Title

Cause of error

Check point & Normal condition

Check Point

1. Check the wire connection. (Open, Soldered poorly)

→ Repair the connection or change the PCB.

2. Check the resistance of float switch (Abnormal : Open, Normal : short)

→ Check the float switch.

3. Check the level of water

4. Check the volt. Of Drain pump power supply. (AC 230V)

→ Repair or Change the main PCB.