beautypg.com

Sidewall direct venting – Lochinvar Shield SNR200-100 User Manual

Page 25

background image

25

3

Sidewall direct venting

(continued)

All vent pipes and air inlets must terminate
at the same height to avoid possibility of
severe personal injury, death, or substantial
property damage.

Multiple vent/air terminations

1. When terminating multiple Shield water heaters terminate

each vent/air connection as described in this manual

(FIG. 3-5A).

ƽ WARNING

2. Place wall penetrations to obtain minimum clearance of

12 inches between edge of air inlet and adjacent vent outlet,
as shown in FIG. 3-5A for U.S. installations. For Canadian
installations, provide clearances required by CSA B149.1
Installation Code.

3. The air inlet of a Shield water heater is part of a direct vent

connection. It is not classified as a forced air intake with
regard to spacing from adjacent water heater vents.

12" MIN. BETWEEN EDGE OF AIR

INLET AND ADJACENT VENT OUTLET

VENT / AIR

TERMINATION

VENT

AIR

Figure 3-5A Multiple Vent Terminations (must also
comply with Figure 3-1A)

Figure 3-5B Alternate Multiple Vent Terminations w/Field
Supplied Fittings (must also comply with Figure 3-1B)

Installation & Service Manual

TM

AIR PIPING

ELBOW

BIRD SCREEN

ELBOW

BIRD SCREEN

SIDEWALL
TERMINATION PLATE

GALVANIZED
THIMBLE

VENT PIPING

Figure 3-4B Alternate Sidewall Termination Assembly
w/Field Supplied Fittings

Prepare wall penetrations (Alternate -

Field Supplied Option)

1. Air pipe penetration:

a. Cut a hole for the air pipe. Size the air pipe hole as

close as desired to the air pipe outside diameter.

2. Vent pipe penetration:

a. Cut a hole for the vent pipe. For either combustible

or noncombustible construction, size the vent pipe

hole with at least a 1/2 inch clearance around the

vent pipe outer diameter:

• 4½ inch hole for 3 inch vent pipe

• 5½ inch hole for 4 inch vent pipe

b. Insert a galvanized metal thimble in the vent pipe

hole as shown in FIG. 3-4B.

3. Use a sidewall termination plate as a template for correct

location of hole centers.

4. Follow all local codes for isolation of vent pipe when

passing through floors or walls.

5. Seal exterior openings thoroughly with exterior caulk.

Termination and fittings

1.

The air termination coupling must be oriented at least
12 inches above grade or snow line as shown in FIG.
3-1A, page 22.

2. Maintain the required dimensions of the finished

termination piping as shown in FIG. 3-1A, page 22.

3. If using the alternate sidewall termination do not extend

exposed vent pipe outside of the building more than what
is shown in this document. Condensate could freeze and
block vent pipe.