Field wiring, Installation must comply with, Line voltage connections – Lochinvar 81 - 286 User Manual
Page 50: Low voltage connections
50
Installation & Operation Manual
8
Field wiring
ELECTRICAL SHOCK HAZARD – For
your safety, turn off electrical power
supply before making any electrical
connections to avoid possible electric
shock hazard. Failure to do so can cause
severe personal injury or death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler
must be replaced, use only type 105°C
wire or equivalent.
Boiler must be electrically grounded as
required by National Electrical Code
ANSI/NFPA 70 – latest edition.
Installation must comply with:
1. National Electrical Code and any other national, state,
provincial, or local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,
and any local codes.
Line voltage connections
1. Connect 120 vac power wiring to the line voltage terminal
strip in the junction box, as shown in FIG. 8-1.
2. Provide and install a fused disconnect or service switch
(15 amp recommended) as required by the code (see
FIG. 8-1).
3. The boiler pump is shipped loose. Wire the boiler pump
as shown in FIG. 8-1.
4. When connecting a domestic hot water (DHW) pump,
connect the wiring to the line voltage terminal strip as
shown in FIG. 8-1.
5. To activate a system pump, wire as shown in FIG. 8-1.
If the motor is larger than 1/8 hp or 1.8 amps, you must
isolate with a relay.
Figure 8-1 Line Voltage Field Wiring Connections
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation.
ƽ WARNING
NOTICE
ƽ CAUTION
Low voltage connections
1. Route all low voltage wires through the knockouts in the
rear of the boiler, as shown in FIG. 8-2.
2. Connect low voltage wiring to low voltage connection
board as shown in FIG. 8-3 on page 53 of this manual and
the boiler wiring diagram.
LOW VOLTAGE
CONNECTION BOARD
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE WIRING KNOCKOUTS
Figure 8-2 Routing Field Wiring